Table 60: Free analogue input, signal selection (Keypad: Menu M2 -> G2.2.6)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.6.1
Scaling of current
limit
0
5
0
399
0 = Not used
1= AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scal-
ing See group G2.9
P2.2.6.2
Scaling of DC-
braking current
0
5
0
400
As parameter
P2.2.6.1 Scaling
from 0 to ID507.
P2.2.6.3
Scaling of acc./
dec. times
0
5
0
401
As parameter
P2.2.6.1 Scales
active ramp from
100 % to 10 %.
P2.2.6.4
Scaling of torque
supervision limit
0
5
0
402
As parameter
P2.2.6.1 Scaling
from 0 to ID348.
P2.2.6.5
Scaling of torque
limit
0
5
0
485
As parameter
P2.2.6.1 Scaling
from 0 to (ID609
(NXS) or ID1287
(NXP)).
NXP drives only
P2.2.6.6
Scaling of genera-
tor torque limit
0
5
0
1087
As parameter
P2.2.6.1 Scaling
from 0 to ID1288.
P2.2.6.7
Scaling of motor-
ing power limit
0
5
0
179
As parameter
P2.2.6.1 Scaling
from 0 to ID1289.
P2.2.6.8
Scaling of genera-
tor power limit
0
5
0
1088
As parameter
P2.2.6.1 Scaling
from 0 to ID1290.
Use TTF programming method for all Digital inputs parameters. See Chapter 8.9 "Terminal
to function" (TTF) programming principle
VACON · 152
MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205