MULTI-STEP SPEED CONTROL APPLICATION
4.1
INTRODUCTION
Select the Multi-step Speed Control Application in menu M6 on page S6.2.
The Multi-step Speed Control Application can be used in applications where fixed speeds are
needed. In total, 15 + 2 different speeds can be programmed: one basic speed, 15 multi-step
speeds and one jogging speed. The speed steps are selected with digital signals DIN3, DIN4,
DIN5 and DIN6. If jogging speed is used, DIN3 can be programmed from fault reset to jogging
speed select.
The basic speed reference can be either voltage or current signal via analogue input
terminals (2/ 3 or 4/5). The other one of the analogue inputs can be programmed for other
purposes.
•
All outputs are freely programmable.
Additional functions:
•
Programmable Start/Stop and Reverse signal logic
•
Reference scaling
•
One frequency limit supervision
•
Second ramps and S-shape ramp programming
•
Programmable start and stop functions
•
DC-brake at stop
•
One prohibit frequency area
•
Programmable U/f curve and switching frequency
•
Autorestart
•
Motor thermal and stall protection: Programmable action; off, warning, fault
The parameters of the Multi-Step Speed Control Application are explained in Chapter 8
Parameter descriptions of this manual. The explanations are arranged according to the
individual ID number of the parameter.
MULTI-STEP SPEED CONTROL APPLICATION
VACON · 69
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
4
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......