A warning or a fault action and message is generated if the 4-20 mA reference signal is used
and the signal falls below 3.0 mA for 5 seconds or below 0.5 mA for 0.5 seconds. The
information can also be programmed into digital output DO1 and relay outputs RO1 and RO2.
701 RESPONSE TO EXTERNAL FAULT 234567 (2.7.3)
Table 167: Selections for parameter ID701
Selection
number
Selection name
Description
0
No response
1
Warning
2
Fault, stop mode after fault
according to ID506
3
Fault, stop mode after fault
always by coasting
A warning or a fault action and message is generated from the external fault signal in the
programmable digital inputs DIN3 or with parameters ID405 and ID406. The information can
also be programmed into digital output DO1 and relay outputs RO1 and RO2.
702 OUTPUT PHASE SUPERVISION 234567 (2.7.6)
Table 168: Selections for parameter ID702
Selection
number
Selection name
Description
0
No response
1
Warning
2
Fault, stop mode after fault
according to ID506
3
Fault, stop mode after fault
always by coasting
Output phase supervision of the motor ensures that the motor phases have an approximately
equal current.
VACON · 320
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205