Table 86: Basic Settings (Control keypad: Menu M2 -> G2.2.1)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.1.8 *
PID actual value
selection
0
7
0
333
0 = Actual value 1
1 = Actual 1 +
Actual 2
2 = Actual 1 -
Actual 2
3 = Actual 1 *
Actual 2
4 = Max (Actual 1,
Actual 2)
5 = Min (Actual 1,
Actual 2)
6 = Mean (Actual 1,
Actual 2)
7 = Sqrt (Act1) +
Sqrt (Act2) See
P2.2.1.9 and
P2.2.1.10
P2.2.1.9 *
Actual value 1
selection
0
5
2
334
0 = Not used
1 = AI1 (control
board)
2 = AI2 (control
board)
3 = AI3
4 = AI4
5 = Fieldbus
(FBProcessDa-
taIN2)
P2.2.1.10
*
Actual value 2
input
0
5
0
335
0 = Not used
1 = AI1 (control
board)
2 = AI2 (control
board)
3 = AI3
4 = AI4
5 = Fieldbus
(FBProcessDa-
taIN3)
P2.2.1.11
Actual value 1
minimum scale
-1600.0
1600.0
%
0.0
336
0 = No minimum
scaling
P2.2.1.12
Actual value 1
maximum scale
-1600.0
1600.0
%
100.0
337
100 = No maximum
scaling
P2.2.1.13
Actual value 2
minimum scale
-1600.0
1600.0
%
0.0
338
0 = No minimum
scaling
P2.2.1.14
Actual value 2
maximum scale
-1600.0
1600.0
%
100.0
339
100 = No maximum
scaling
PUMP AND FAN CONTROL APPLICATION
VACON · 207
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
7
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......