6.4.3
INPUT SIGNALS
Table 55: Basic Settings (Control keypad: Menu M2 -> G2.2.1)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
Start/P2.2.1.1 **
Stop logic selec-
tion
0
7
0
300
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run ena-
ble
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Start
Ctrl sgn 2 = Motor
potentiometer UP
Logic = 5
Ctrl sgn 1 = Forward
pulse (edge)
Ctrl sgn 2 = Reverse
pulse (edge)
Logic = 6
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Reverse
pulse
Logic = 7
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Enable
pulse
MULTI-PURPOSE CONTROL APPLICATION
VACON · 145