Table 36: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.28
Motor potentiom-
eter frequency
reference mem-
ory reset
0
2
1
367
0 = No reset
1 = Reset if stop-
ped or powered
down
2 = Reset if pow-
ered down
P2.2.29
Motor potentiom-
eter PID reference
memory reset
0
2
0
370
0 = No reset
1 = Reset if stop-
ped or powered
down
2 = Reset if pow-
ered down
P2.2.30
PID minimum
limit
-1600.0
P2.2.31
%
0.0
359
P2.2.31
PID maximum
limit
P2.2.30
1600.0
%
100.0
360
P2.2.32
Error value inver-
sion
0
1
0
340
0 = No inversion
1 = Inversion
P2.2.33
PID reference ris-
ing time
0.1
100.0
s
5.0
341
P2.2.34
PID reference
falling time
0.1
100.0
s
5.0
342
P2.2.35
Reference scaling
minimum value,
place B
0.00
320.0
Hz
0.00
344
P2.2.36
Reference scaling
maximum value,
place B
0.00
320.0
Hz
0.00
345
P2.2.37
Easy changeover
0
1
0
366
0 = Keep reference
1 = Copy actual
reference
P2.2.38
***
AI3 signal selec-
tion
0.1
E.10
0.1
141
TTF programming
method used. See
VACON · 108
PID CONTROL APPLICATION
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...