Table 26: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.9
****
AI2 signal selec-
tion
0.1
E.10
A.2
388
TTF programming
method used. See
P2.2.10
AI2 signal range
0
2
1
325
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
P2.2.11
AI2 custom set-
ting minimum
-160.00
160.00
%
0.00
326
Analogue input 2
scale minimum.
P2.2.12
AI2 custom set-
ting maximum
-160.00
160.00
%
100.00
327
Analogue input 2
scale maximum.
P2.2.13
AI2 signal inver-
sion
0
1
0
328
Analogue input 2 ref-
erence inversion
yes/no.
P2.2.14
AI2 signal filter
time
0.00
10.00
s
0.10
329
Analogue input 2 ref-
erence filter time,
constant.
P2.2.15
Reference scaling
minimum value
0.00
320.00
Hz
0.00
303
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
P2.2.16
Reference scaling
maximum value
0.00
320.00
Hz
0.00
304
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
0.00 = No scaling
>0 = scaled max.
value
P2.2.17
Free analogue
input, signal
selection
0
2
0
361
0 = Not used
1 = AI1
2 = AI2
MULTI-STEP SPEED CONTROL APPLICATION
VACON · 79
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
4
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......