Table 143: Selections for parameter ID371
Selection
number
Selection name
Description
0
AI1 reference
(terminals 2 and 3, e.g. potentiometer)
1
AI2 reference
(terminals 5 and 6, e.g. transducer)
2
AI3 reference
3
AI4 reference
4
PID reference 1 from keypad
5
Reference from Fieldbus
(FBProcessDataIN3)
see Chapter 8.7 Fieldbus control parameters (IDs 850 to 859)
6
Motor potentiometer
If value 6 is selected for this parameter, the functions Motor
potentiometer DOWN and Motor potentiometer UP must be
connected to digital inputs (parameters ID417 and ID418).
7
PID reference 2 from keypad
372 SUPERVISED ANALOGUE INPUT 7 (2.3.2.13)
Table 144: Selections for parameter ID372
Selection
number
Selection name
Description
0
Analogue input 1 (AI1)
1
Analogue input 2 (AI2)
373 ANALOGUE INPUT LIMIT SUPERVISION 7 (2.3.2.14)
If the value of the selected analogue input goes under/over the set supervision value
(parameter ID374) this function generates a message through the digital output or the relay
outputs depending on to which output the analogue input supervision function (parameter
ID463) is connected.
Table 145: Selections for parameter ID373
Selection
number
Selection name
Description
0
No supervision
1
Low limit supervision
2
High limit supervision
VACON · 284
PARAMETER DESCRIPTIONS
8
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205