Table 56: Analogue input 1 (Control keypad: Menu M2 -> G2.2.2)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.2.1
**
AI1 signal selec-
tion
0.1
E.10
A.1
377
TTF programming.
See Chapter 8.9
P2.2.2.2
AI1 filter time
0.00
320.00
s
0.10
324
Filters out distur-
bances from the
incoming analogue
signal.
P2.2.2.3
AI1 signal range
0
3
0
320
0 = 0-10 V (0-20
mA*)
1 = 2-10 V (4-20
mA*)
2 = -10V...+10 V*
3 = Custom range
*
P2.2.2.4
AI1 custom mini-
mum setting
-160.00
160.00
%
0.00
321
The percentage of
input signal range.
For example, 3 V =
30%.
P2.2.2.5
AI1 custom maxi-
mum setting
-160.00
160.00
%
100.00
322
For example 9 V =
90%.
P2.2.2.6
AI1 reference
scaling, minimum
value
0.00
320.00
Hz
0.00
303
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
P2.2.2.7
AI1 reference
scaling, maximum
value
0.00
320.00
Hz
0.00
304
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
P2.2.2.8
AI1 joystick hyste-
resis
0.00
20.00
%
0.00
384
When the refer-
ence is between 0
and 0 ± this
parameter, the
reference is set to
0.
P2.2.2.9
AI1 sleep limit
0.00
100.00
%
0.00
385
The AC drive goes
to sleep mode if
input is below this
limit for set time.
P2.2.2.10
AI1 sleep delay
0.00
320.00
s
0.00
386
MULTI-PURPOSE CONTROL APPLICATION
VACON · 147
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
6
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......