7.4.3
INPUT SIGNALS
Table 86: Basic Settings (Control keypad: Menu M2 -> G2.2.1)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.1.1 *
I/O B frequency
reference selec-
tion
0
7
0
343
0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad refer-
ence
5 = Fieldbus refer-
ence (FB Spee-
dReference)
6 = Motor potenti-
ometer
7 = PID controller
P2.2.1.2 *
Keypad control
reference selec-
tion
0
7
4
121
As in P2.2.1.1
P2.2.1.3 *
Fieldbus control
reference selec-
tion
0
7
5
122
As in P2.2.1.1
P2.2.1.4 *
PID Reference 2
0
7
7
371
0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = PID reference
1 from keypad
5 = Fieldbus refer-
ence (FBProcess-
DataIN3)
6 = Motor potenti-
ometer
7 = PID reference
2 from keypad
P2.2.1.5
PID error value
inversion
0
1
0
340
0 = No inversion
1 = Inversion
P2.2.1.6
PID reference ris-
ing time
0.1
100.0
s
5.0
341
Time for reference
value to change
from 0% to 100%
P2.2.1.7
PID reference
falling time
0.1
100.0
s
5.0
342
Time for reference
value to change
from 100% to 0%
VACON · 206
PUMP AND FAN CONTROL APPLICATION
7
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205