Table 88: Analogue input 2 (Control keypad: Menu M2 -> G2.2.3)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.3.1
**
AI2 signal selec-
tion
0.1
E.10
A.2
388
TTF programming.
See Chapter 8.9
P2.2.3.2
AI2 filter time
0.00
10.00
s
0.10
329
0 = No filtering
P2.2.3.3
AI2 signal range
0
2
1
325
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
P2.2.3.4
AI2 custom mini-
mum setting
-160.00
160.00
%
0.00
326
P2.2.3.5
AI2 custom maxi-
mum setting
-160.00
160.00
%
100.00
327
P2.2.3.6
AI2 inversion
0
1
0
328
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
VACON · 210
PUMP AND FAN CONTROL APPLICATION
7