3.4.4
OUTPUT SIGNALS (CONTROL KEYPAD: MENU M2 -> G2.3
Table 17: Output signals, G2.3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.1
AO1 signal selec-
tion
0.1
E.10
A11
464
TTF programming
method used. See
P2.3.2
Analogue output
function
0
8
1
307
0 = Not used (20
mA/10V)
1 = Output freq. (0-
f
max
)
2 = Freq. refer-
ence (0-f
max
)
3 = Motor speed
(0-Motor nominal
speed)
4 = Motor current
(0-I
nMotor
)
5 = Motor torque
(0-T
nMotor
)
6 = Motor power
(0-P
nMotor
)
7 = Motor voltage
(0-U
nMotor
)
8 = DC-link volt
(0-1000V)
P2.3.3
Analogue output
filter time
0.00
10.00
s
1.00
308
0 = No filtering
P2.3.4
Analogue output
inversion
0
1
0
309
0 = Not inverted
1 = Inverted
P2.3.5
Analogue output
minimum
0
1
0
310
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.6
Analogue output
scale
10
1000
%
100
311
LOCAL/REMOTE CONTROL APPLICATION
VACON · 55
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
3
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......