Table 16: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.17
Place A Reference
scaling maximum
value
0.00
304
Selects the fre-
quency that corre-
sponds to the max.
reference signal 0.00
= No scaling >0 =
scaled max. value.
P2.2.18
Place B Reference
scaling minimum
value
0.00
320.00
Hz
0.00
364
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
P2.2.19
Place B Reference
scaling maximum
value
0.00
320.00
Hz
0.00
365
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
0.00 = No scaling
>0 = scaled max.
value
P2.2.20
Free analogue
input, signal
selection
0
2
0
361
0 = Not used
1 = Analogue input 1
2= Analogue input 2
P2.2.21
Free analogue
input, function
0
4
0
362
0 = No reset
1 = Reduces current
limit (P2.1.5)
2 = Reduces DC
braking current
3 = Reduces accel.
and decel. times
4 = Reduces torque
super vision limit
P2.2.22
Motor potentiom-
eter ramp time
0.1
2000.0
Hz/s
10.0
331
P2.2.23
Motor potentiom-
eter frequency
reference mem-
ory reset
0
2
1
367
0 = No reset
1 = Reset if stopped
or powered down
2 = Reset if powered
down
P2.2.24
Start pulse mem-
ory
0
1
0
498
0 = Run state not
copied
1 = Run state copied
** = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
LOCAL/REMOTE CONTROL APPLICATION
VACON · 53
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
3
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......