Table 2: Basic parameters G2.1
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.17
DIN3 function
0
7
1
301
0 = Not used
1 = Ext. fault, clos-
ing cont.
2 = Ext. fault,
opening cont.
3 = Run enable, cc
4 = Run enable, oc
5 = Force cp. to IO
6 = Force cp. to
keypad
7 = Force cp. to
fieldbus
P2.18
Preset speed 1
0.00
P2.2
Hz
0.00
105
Speeds preset by
operator
P2.19
Preset speed 2
0.00
P2.2
Hz
50.00
106
Speeds preset by
operator
P2.20
Automatic restart
0
1
0
731
0 = Disabled
2 = Enabled
1.4.3
KEYPAD CONTROL (CONTROL KEYPAD: MENU M3)
The parameters for the selection of control place and direction on the keypad are listed
below. See the Keypad control menu in the product's User Manual.
Table 3: Keypad control parameters, M3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P3.1
Control place
1
3
1
125
1 = I/0 terminal
2 = Keypad
3 = Fieldbus
P3.2
Keypad reference
P2.1
P2.2
Hz
0.00
P3.3
Direction (on key-
pad)
0
1
0
123
You can adjust the
frequency refer-
ence on the keypad
with this parame-
ter.
R3.4
Stop button
0
1
1
114
0 = Limited func-
tion of Stop button
1 = Stop button
always enabled
BASIC APPLICATION
VACON · 17
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
1
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......