303 REFERENCE SCALING, MINIMUM VALUE 2346 (2.2.4, 2.2.16, 2.2.2.6)
304 REFERENCE SCALING, MAXIMUM VALUE 2346 (2.2.5, 2.2.17, 2.2.2.7)
Additional reference scaling. If both parameter ID303 and parameter ID304 = 0 scaling is set
off. The minimum and maximum frequencies are used for scaling.
NOTE!
This scaling does not affect the fieldbus reference (scaled between Minimum
frequency (parameter ID101) and Maximum frequency (parameter ID102).
f
out
f
out
10
0
ID303
ID304
10
0
f
max
ID102
f
min
ID101
f
max
ID102
f
min
ID101
AI [V]
AI [V]
Fig. 34: Left: Reference scaling; Right: No scaling used (parameter ID303 = 0)
305 REFERENCE INVERSION 2 (2.2.6)
Inverts reference signal:
Max. input signal = Min. freq. reference
Min. input signal = Max. freq. reference
Table 118: Selections for parameter ID305
Selection
number
Selection name
Description
0
No inversion
1
Reference inverted
PARAMETER DESCRIPTIONS
VACON · 255