Table 37: Output signals, G2.3
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.3.6
Analogue output
scale
10
1000
%
100
311
P2.3.7
Digital output 1
function
0
23
1
312
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat
warning
6 = Ext. fault or
warning
7 = Ref. fault or
warning
8 = Warning
9 = Reversed
10 = Preset speed
1
11 = At speed
12 = Mot. regulator
active
13 = OP freq. limit
superv. 1
14 = OP freq. limit
superv.2
15 = Torque limit
superv.
16 = Ref. limit
superv.
17 = Ext. brake
control
18 = Control place:
IO
19 = FC temp. limit
superv.
20 = Unrequested
rotation direction
21 = Ext. brake
control inverted
22 = Thermistor
fault/warn.
23 = Fieldbus DIN1
P2.3.8
RO1 function
0
23
2
313
As parameter 2.3.7
P2.3.9
RO2 function
0
23
3
314
As parameter 2.3.7
P2.3.10
Output frequency
limit 1 supervision
0
2
0
315
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
VACON · 112