3.4.9
AUTORESTART PARAMETERS (CONTROL KEYPAD: MENU M2 -> G2.8)
Table 22: Autorestart parameters, G2.8
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.8.1
Wait time
0.10
10.00
s
0.50
717
The wait time
before the first
reset is done.
P2.8.2
Trial time
0.00
60.00
s
30.00
718
When the trial time
is over, and the
fault is still active,
the drive will trip.
P2.8.3
Start function
0
2
0
719
The selection of
the start mode for
Automatic reset.
0 = Ramp
1 = Flying start
2 = According to
P2.4.6
P2.8.4
Number of tries
after undervoltage
trip
0
10
0
720
P2.8.5
Number of tries
after overvoltage
trip
0
10
0
721
P2.8.6
Number of tries
after overcurrent
trip
0
3
0
722
P2.8.7
Number of tries
after 4mA refer-
ence trip
0
10
0
723
P2.8.8
Number of tries
after motor tem-
perature fault trip
0
10
0
726
P2.8.9
Number of tries
after external
fault trip
0
10
0
725
P2.8.10
Number of tries
after underload
fault trip
0
10
0
738
3.4.10
KEYPAD CONTROL (CONTROL KEYPAD: MENU M3)
The parameters for the selection of control place and direction on the keypad are listed
below. See the Keypad control menu in the product's User Manual.
LOCAL/REMOTE CONTROL APPLICATION
VACON · 67
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
3
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......