Table 36: Input signals, G2.2
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.16
AI1 signal range
0
2
0
320
0 = 0—10 V (0—20
mA*)
1 = 2—10 V (4 – 20
mA*)
2 = Custom range*
P2.2.17
AI1 custom mini-
mum setting
–160.00
160.00
%
0.00
321
P2.2.18
AI1 custom maxi-
mum setting
–160.00
160.00
%
100.0
322
P2.2.19
AI1 inversion
0
1
0
323
0 = Not inverted
1 = Inverted
P2.2.20
AI1 filter time
0.00
10.00
s
0.10
324
0 = No filtering
P2.2.21
AI2 signal selec-
tion
0.1
E.10
A.2
388
0 = 0—20 mA (0—
10 V *)
1 = 4 – 20 mA (2—
10 V *)
2 = Custom range*
P2.2.22
AI2 signal range
0
2
1
325
0 = 0—20 mA*
1 = 4—20 mA*
2 = Customised*
P2.2.23
AI2 custom mini-
mum setting
-160.00
160.00
%
0.00
326
P2.2.24
AI2 custom maxi-
mum setting
-160.00
160.00
%
0.00
327
P2.2.25
AI2 inversion
0
1
0
328
0 = Not inverted
1 = Inverted
P2.2.26
AI2 filter time
0.00
10.00
s
0.10
329
0 = No filtering
P2.2.27
Motor potentiom-
eter ramp time
0.1
2000.0
Hz/s
10.0
331
PID CONTROL APPLICATION
VACON · 107
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]