Table 34: Monitoring values
Index
Monitoring value
Unit
ID
Description
V1.1
Output frequency
Hz
1
The output frequency to motor
V1.2
Frequency reference
Hz
25
The frequency reference to motor control
V1.3
Motor speed
rpm
2
The actual speed of the motor in rpm
V1.4
Motor current
A
3
V1.5
Motor torque
%
4
The calculated shaft torque
V1.6
Motor power
%
5
The calculated motor shaft power in percentage
V1.7
Motor voltage
V
6
The output voltage to motor
V1.8
DC link voltage
V
7
The measured voltage in the DC-link of the drive
1.9
Unit temperature
°C
8
The heatsink temperature in Celsius or Fahrenheit
1.10
Motor temperature
%
9
The calculated motor temperature in percentage
of the nominal working temperature
V1.11
Analogue input 1
V/mA
13
AI1
V1.12
Analogue input 2
V/mA
14
AI2
V1.13
Analogue input 3
27
AI3
V1.14
Analogue input 4
28
AI4
V1.15
DIN 1, 2, 3
15
Shows the status of the digital inputs 1-3
V1.16
DIN 4, 5, 6
16
Shows the status of the digital inputs 4-6
V1.17
DO1, RO1, RO2
17
Shows the status of the digital and relay outputs
1-3
V1.18
Analogue I
out
mA
26
AO1
V1.19
PID Reference
%
20
In % of the max. frequency
V1.20
PID Actual value
%
21
In % of the max. actual value
V1.21
PID Error value
%
22
The error value of the PID controller. It is the devi-
ation of feedback from the setpoint in process
units. You can use a parameter to make the selec-
tion of the process unit.
V1.22
PID Output
%
23
The PID output as a percentage (0-100%). It is pos-
sible to give this value to the motor control (fre-
quency reference) or to an analogue output.
V1.23
Special display for
actual value
29
See parameters 2.2.46 to 2.2.49
PID CONTROL APPLICATION
VACON · 99
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
5
Содержание NX series
Страница 1: ...vacon nx ac drives all in one application manual ...
Страница 2: ......
Страница 5: ...VACON 5 24 HOUR SUPPORT 358 0 201 212 575 EMAIL VACON VACON COM ...
Страница 6: ...VACON 6 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 391: ......