Table 90: Analogue input 4 (Control keypad: Menu M2 -> G2.2.5)
Index
Parameter
Min
Max
Unit
Default
Cust
ID
Description
P2.2.5.1
**
AI4 signal selec-
tion
0.1
E.10
0.1
152
TTF programming.
See Chapter 8.9
P2.2.5.2
AI4 filter time
0.00
10.00
s
0.00
153
0 = No filtering
P2.2.5.3
AI4 signal range
0
2
1
154
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
P2.2.5.4
AI4 custom mini-
mum setting
-160.00
160.00
%
0.00
155
% of input signal
range. e.g. 2 mA =
10 %
P2.2.5.5
AI4 custom maxi-
mum setting
-160.00
160.00
%
100.00
156
e.g. 18 mA = 90 %
P2.2.5.6
AI4 signal inver-
sion
0
1
0
162
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
VACON · 212
PUMP AND FAN CONTROL APPLICATION
7
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205