O & M Manual IM05805023K

Effective

 June

 2012

EATON XTJP / XTJY

Jockey Pump Controllers

Содержание Jockey XTJP

Страница 1: ...O M Manual IM05805023K Effective June 2012 EATON XTJP XTJY Jockey Pump Controllers ...

Страница 2: ...CHECKOUT INSTRUCTIONS 4 3 1 1 Motor Rotation Check 4 3 1 2 Starting and Stopping 4 3 1 3 Motor Circuit Protector Overload Relay Trip Setting 4 3 1 4 Circuit Breaker Trip Settings 4 3 1 5 Run Period Timer Optional 4 FIGURE 1 ELECTRICAL WIRING SCHEMATIC Three Phase 5 FIGURE 2 DIMENSIONAL DRAWING NEMA 2 6 FIGURE 3 ELECTRICAL WIRING SCHEMATIC WYE DELTA Star Delta 7 FIGURE 4 DIMENSIONAL DRAWING WYE DEL...

Страница 3: ...em pressure connection located on the bottom external side of the enclosure The connection should be installed as per NFPA pamphlet No 20 NOTE Water lines to the pressure transducer must be free from dirt and contamination The pressure should not exceed what the pressure transducer is rated for 3 Electrical Connections All electrical connections should meet national and local electrical codes and ...

Страница 4: ...above the pressure stop point 1Lo HYS For manual operation set the H O A selector switch to HAND to start the pump and OFF to stop 3 1 3 Motor Circuit Protector Overload Relay Trip Setting The trip setting should be set to match the motor nameplate full load amps 3 1 4 Circuit Breaker Trip Settings When a Circuit Breaker is installed the trip setting must be set as indicated on the chart on the in...

Страница 5: ...ure 1 Electrical Wiring Schematic Three Phase 3 1 M 4 2 3 4 DPM T1 M CFU H2 H1 120V 1F X1 X2 TR M 1L3 1L1 1L2 L2 L3 L1 T2 T3 M F1 F2 DPM SUPPLY OUTPUT DPM TRANSDUCER PRESSURE BLUE BROWN SIGNAL I P LEGEND M CONTACTOR CFU CONTROL FUSE DPM DIGITAL PANEL METER PROTECTOR MOTOR CIRCUIT RELAY 1 GND HAND MOTOR AUTO OFF N Y C APPROVED ...

Страница 6: ...and Rating kA Motor Hp Withstand Rating kA Motor Hp Withstand Rating kA 0 33 3 65 0 33 3 65 0 33 5 65 0 33 7 5 65 0 33 10 18 4 50 4 50 7 5 10 18 10 50 5 10 18 5 10 18 15 20 18 120V 1Ø 240V 1Ø Approx Weight NOTES 1 All enclosures finished in Red 2 Cable Entrance either top or bottom 3 Standard Enclosure type NEMA 2 Motor Hp Withstand Rating kA Motor Hp Withstand Rating kA Lbs Kg 0 33 0 5 65 0 33 2 ...

Страница 7: ...M DPM 3 4 T5 T4 T6 X1 H1 CFU 1F L2 120V X2 TR H2 1S 1M 2M 1L3 1L1 1L2 F1 F2 PROTECTOR OFF AUTO HAND SUPPLY INTERLOCK MECHANICAL LEGEND 1M START CONTACTOR 1S WYE POINT CONTCATOR 2M RUN CONTACTOR OL MOTOR OVERLOAD CFU CONTROL FUSE AT ACCELERATION TIMER FACTORY SET 2 SECONDS DPM DIGITAL PANEL METER NOTES 1 ALL RELAY CONTACTS ARE SHOWN IN NO POWER CONDITION MOTOR MOTOR CIRCUIT OUTPUT RELAY1 DPM TRANSD...

Страница 8: ... 4 50 7 5 10 18 10 50 5 10 18 5 10 18 15 20 18 120V 1Ø 240V 1Ø Approx Weight NOTES 1 All enclosures finished in Red 2 Cable Entrance either top or bottom 3 Standard Enclosure type NEMA 2 Motor Hp Withstand Rating kA Motor Hp Withstand Rating kA Lbs Kg 0 33 0 5 65 0 33 2 65 22 10 0 75 50 3 5 18 1 2 18 21 76 553 16 38 416 13 00 330 8 08 205 16 00 406 21 15 537 2 63 67 3 96 101 8 60 218 Ø 0 27 Ø7 x4 ...

Страница 9: ...FF position Apply power to the Jockey Pump Controller Once power is applied turn the Rotary Disconnect switch to the ON position NOTE The instructions below are based on the factory default settings Displayed values may vary depending on the programmed parameter setpoint values Factory default settings for each parameter are listed in Table 1 4 1 1 Intial Setup The Digital Display will show the cu...

Страница 10: ...change the setting 4 1 6 RELAY 1 Hi ALARM SETPOINT 9999 While holding the PGM button press the UP Arrow button The display will show 1Hi Release the UP Arrow and PGM buttons The display will show 9999 Do not change the setting 4 1 7 RELAY 1 Lo ALARM SETPOINT 0000 Pressure Start Point While holding the PGM button press the UP Arrow button The display will show 1Lo Release the UP Arrow and PGM butto...

Страница 11: ...ing the UP and Down Arrow buttons eg Start Setpoint 0100psi and the desired Stop Setpoint is 115 psi Set the HYS differential to 0015 Note The minimum differential setting is 1psi 0001 4 1 11 RUN While holding the PGM button press the UP Arrow button The display will show run Release the UP Arrow and PGM buttons The current pressure is displayed PGM PGM PGM 2Lo HYS run 9999 0000 XXX Current System...

Страница 12: ...F TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will EATON be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any special indirect incidental or consequential damage or loss whatsoever including but not limited to damage or loss of use of equipment plant or power system cost of ...