2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
P04
Motor (Auto-tuning)
The inverter automatically detects the motor parameters and saves them in its internal memory.
Basically, it is not necessary to perform tuning when a Fuji standard motor is used with a standard
connection with the inverter.
P04 = 1, 2, and 3 are only for asynchronous motors. P04 = 4 can be used for both types of motors.
For synchronous motors, the magnetic pole position offset tuning (L03) should be executed.
P04
data
Auto-tuning
Action
Motor parameters to be tuned
0
Disable
—
—
1
Tune the motor
while it is stopped
Tune %R1 and %X while
the motor is stopped
Primary resistance (%R1)
(P07)
Leakage reactance (%X)
(P08)
2
Tune the motor
while it is stopped
Tune %R1, %X, no-load
current, and rated slip
while the motor is stopped
No-load current
(P06)
Primary resistance (%R1)
(P07)
Leakage reactance (%X)
(P08)
Rated slip frequency
(P12)
3
Tune the motor
while it is stopped
No-load current is
calculated.Others are
same as the P04 = 2.
No-load current
(P06)
Primary resistance (%R1)
(P07)
Leakage reactance (%X)
(P08)
Rated slip frequency
(P12)
4
(Reserved)
—
—
In any of the following cases, perform auto-tuning. This is because you may not obtain
the best performance under the PG vector control since the motor parameters are different
from that of Fuji standard motors.
•
The motor to be driven is a non-Fuji motor or a non-standard motor.
•
Cabling between the motor and the inverter is long. (Generally, 20 m (66 ft) or longer)
•
A reactor is inserted between the motor and the inverter.
Other applicable cases
2-85
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...