Inputs 1 and 2 (U02, U03, U07, U08, etc.)(Analog)
The following signals are available as analog input signals.
Data
Selectable Signals
8000
General-purpose analog output signal (same as signals selected in F31: output
frequency 1, output current, output torque, Input power, DC link bus voltage,
etc.)
Example: For output frequency 1, maximum frequency (100%) is input as
100.00.
Example: For output current, 200% of the inverter rated current is input as
100.00.
Note: 10 (Universal AO) is not available.
to
8019
2001 to 2200
Output of step 1 to 200 “SO001” to “SO200”
9001
Analog 12 terminal input signal [12]
9002
Analog C1 terminal input signal [V2] (C1 function)
9003
Analog V2 terminal input signal [V2] (V2 function)
■
Function 1, Function 2 (U04, U05, U09, U10, etc.)(Analog)
Sets the upper limit and lower limit of function block operation.
Data
Function
Description
-9990.00 to 0.00
to +9990.00
Reference value
Hysteresis width
Upper limit
Lower limit
Upper threshold
Lower threshold
Setting values for the operation of the function block
(selected with the corresponding function code such as
U01).