2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
Auto Reset (Mode selection 1) (H81)
The alarm codes enabled on H81 bits will be auto-reset according to H04 and H05 setting. In other
words, a specific function code can be auto-reset only if dedicated bit is set to 1. Table below shows
the bit crossreference with alarm codes. The setting on H81 takes priority over H82.
Alarm codes crossreference with H81 bits.
15 14 13
12
11 10
9
8
7
6
5
4
3
2
1
0
-
- Eo OH6 -
-
Er6
*1
ErE OL1 OH4 OH3 OH1 OLU LV OVn
*2
OCn
*2
*1
Only for subcode 8 and 14 (failure in brake sequences). If cause is due to another subcode, alarm
code will not be auto reset.
*2
Only for subcode 10 or lower. If subcode 11 or higher occurs, alarm code will not be auto reset.
- Example: H81=012Fh (ErE, OH3, OLU, LV, OVn and OCn can be auto-reset).
Auto Reset (Mode selection 2) (H82)
The alarm codes enabled on H82 bits can be auto-reset infinite times, alarm will be reset after H05
time is elapsed. A specific function code can be auto-reset only if dedicated bit is set to 1. Table
below shows the bit crossreference with alarm codes. The setting on H81 takes priority over H82.
Therefore if bit 2 is set to 1 in H81 and H82, alarm code LV will be reset only H04 times (not
infinite times).
Alarm codes crossreference with H82 bits.
15 14 13
12
11 10
9
8
7
6
5
4
3
2
1
0
-
- Eo OH6 -
-
Er6
*1
ErE OL1 OH4 OH3 OH1 OLU LV OVn
*2
OCn
*2
*1
Only for subcode 8 and 14 (failure in brake sequences). If cause is due to another subcode, alarm
code will not be auto reset.
*2
Only for subcode 10 or lower. If subcode 11 or higher occurs, alarm code will not be auto reset.
- Example: H81=012Fh (ErE, OH3, OLU, LV, OVn and OCn can be auto-reset).
The auto-reset state can be monitored from the external equipment via a digital output
terminal to which the
TRY
signal by setting "26" with E20 to E24 and E27.
The auto-reset function is disabled while auto-tuning or pole position offset tuning are
performed.
H06
Cooling Fan Control
H06 specifies the ON-duration of the cooling fan. To prolong the life of the cooling fan and reduce
fan noise during running, the cooling fan stops when the temperature inside the inverter drops below
a certain level.
Setting the H06 data to 0.0 automatically turns the cooling fan ON/OFF depending upon the
temperature even when the inverter is running.
The cooling fan does not restart for 10 seconds after stopping.
- Data setting range: Auto (Auto ON/OFF depending upon temperature)
0.5 to 10.0 (min.)
OFF (Disable. Always ON)
The cooling fan state can be monitored via a digital output terminal to which the
FAN
is
assigned by setting "25."
2-91
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...