2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
Function code data
Terminal commands assigned
Symbol
Active ON
Active OFF
101
1101
External alarm 2
THR2
102
1102
Start reference torque decreasing
RTDEC
103
1103
Inverter Output MC confirmation
CS-MC
108
1108
CAN Enable
CAN_LE
111
1111
Check brake control 1
BRKE1
112
1112
Check brake control 2
BRKE2
114
1114
Enable rescue operation by means of brake control
RBRK
115
1115
Short-circuit control feedback
SCCF
117
1117
Stand-by mode
STBY
118
-
Unlocking safty gear operation
ULSG
Any negative logic (Active OFF) command can be assigned to the functions marked with
"
-
" in the "Active OFF" column.
The "Enable external alarm trip" and "Force to decelerate" are fail-safe terminal
commands. For example, when data = "9" in "Enable external alarm trip", it becomes
Active OFF (alarm is triggered when OFF); when data = 1009, it becomes Active ON
(alarm is triggered when ON).
Terminal function assignment and data setting
■
Select multistep speed -- SS1, SS2,SS4 and SS8
(Function code data = 0, 1, 2, and 3)
The combination of the ON/OFF states of digital input signals
SS1
,
SS2
,
SS4
and
SS8
selects one of
16 different frequency commands defined beforehand by 16 function codes C04 to C19
(Multi-frequency 0 to 15). With this, the inverter can drive the motor at 16 different preset
frequencies.
For details, refer to the description of function code F01 (Speed Command).
■
Coast to a stop --
BX
(Function code data = 7)
Turning this terminal command ON immediately stops the inverter output so that the motor coasts to
a stop without issuing any alarm. Turning it OFF restarts the inverter.
■
Reset alarm --
RST
(Function code data = 8)
Turning this terminal command ON clears the
ALM
state, alarm output (for any alarm). Turning it
OFF erases the alarm display and clears the alarm hold state. When you turn the
RST
command ON,
keep it ON for 10 ms or more. This command should be kept OFF for the normal inverter operation.
2-51
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...