The content of the previous page is recorded in the following tables.
Data for L90
(PG Error
Detection Mode)
PG error detection conditions
If a PG error is detected, the inverter:
Outputs
ALM
Trips with alarm
indication
Outputs
PG-ABN
0
The speed is within domains
through
in the above graph
during the detection time (L92).
OFF
---
ON
1
ON
ErE
OFF
2
The speed is within domains
through
in the above graph
during the detection time (L92).
3
The speed is within domains
or
in the below graph during
the detection time (H77).
The speed is within domains
through
in the below graph
during the detection time (L92).
ON
ErE
OFF
L93
Overheat Early Warning Level
When the temperature reaches the overheat early warning level that is
n
°
C below the trip level, the
inverter issues an overheat early warning signal. L93 specifies the
n
°
C. The early warning signal
OH
is assigned to a general-purpose, programmable output terminal by setting E20 to E24 and E27 to
“28”.
- Data setting range: 1 to 20 (deg)
ON conditions
OFF conditions
Current status
retained
When any of the following conditions is
met, the
OH
signal is turned ON.
- The heat sink temperature is higher
than "Heat sink overheat trip
temperature - L93 setting."
- The inverter inside temperature is
higher than "Internal overheat trip
temperature - L93 setting."
- The IGBT junction temperature is
higher than "Inverter overload trip
temperature - L93 setting."
When all of the following conditions
are met, the
OH
signal is turned OFF.
- The heat sink temperature is lower
than "Heat sink overheat trip
temperature - L93 setting - 3
°
C."
- The inverter inside temperature is
lower than "Internal overheat trip
temperature - L93 setting - 3
°
C."
- The IGBT junction temperature is
lower than "Inverter overload trip
temperature - L93 setting - 3
°
C."
Except the
conditions listed at
left
Trip level
Early warning OFF level
L93 setting
3
℃
OH
ON
OFF
OFF
Early warning ON level
2-172
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...