L55
Torque Bias (Startup time)
L55 specifies the startup time of the torque bias.
- Data setting range: 0.00 to 1.00 (s)
Terminal command "Hold torque bias" and startup time
Setting "62" to any general-purpose, programmable input terminal (by function codes E01 to E08,
E98 and E99) assigns the
H-TB
command.
Turning the
H-TB
ON holds the reference torque bias; turning it OFF releases the hold.
When a run command
FWD
or
REV
is turned ON, the inverter increases the reference torque bias
value to the specified torque bias in the time length proportional to L55. Note that L55 specifies the
time length required from the start of running until the torque changes from 0 to 100% of the motor
rated torque. Once the reference torque bias value reaches the specified one, the bias setting applies.
ON
ON
Hold
Turning ON
FWD
/
REV
then
H-TB
H-TB
FWD
/
REV
Analog input
(Torque bias)
or PI output
Reference
torque bias
FWD
/
REV
ON
increases torque bias
to the setting
ON
ON
Turning ON
H-TB
then
FWD
/
REV
Torque bias setting
upon activating
H-TB
(Torque bias reference value (%)/Rated torque)
x
Startup time (L55)
When the PI torque bias (L54=2) is set, it is necessary to turn on the
FWD
or
REV
earlier than
H-TB
.
2-158
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...