Function codes for the customizable logic
Function code
number
Name
Range
Minimum unit
Remarks
U121 to U140 User parameter 1 to 20
-9990.00 to 9990.00
Effective number are 3 digits.
0.01 to 10
U171 to U175 Storage area 1 to 5
-9990.00 to 9990.00
Effective number are 3 digits.
0.01 to 10
Memorize the
data at power
off.
■
Configuration of function codes
Set a function code group (code from the following table) to function 1 (such as U04) and set the last
two digits of the function code number to function 2 (such as U05) to specify individual function
codes.
Group
Code
Name
Group
Code
Name
F
0
Basic function
L1
56
Lift function
E
1
Terminal function
L2
57
Lift function
C
2
Control function
K
28
Keypad function
P
3
Motor1
M
8
Monitor
H
4
High performance function
W
15
Monitor 2
H1
31
High performance function
W1
22
Monitor 3
U
11
Customizable logic
W2
23
Monitor 4
U1
39
Customizable logic
X
16
Alarm 1
y
14
Link function
Z
17
Alarm 2
L
9
Lift function
■
Task process cycle setting (U100)
U100 data
Data
0
Automatically adjusts the task cycle from 2 ms to 10 ms depending on the number of
used steps. This is the factory default. It is recommended to use this value.
2
2 ms: Up to 10 steps. If it exceeds 10 steps, the customizable logic does not work.
5
5 ms: Up to 50 steps. If it exceeds 50 steps, the customizable logic does not work.
10
10 ms: Up to 100 steps. If it exceeds 100 steps, the customizable logic does not work.
20
20 ms Up to 200 steps.
Note that if the number of steps defined in 2, 5 or 10 is exceeded, the customizable logic does not
work.
2-130
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...