Compatibility selection (y37)
Specifies CANopen behaviour as keeping compatibility with FRENIC-Lift (LM1).
To change the y37 data, it is necessary to press the
+
/
keys (simultaneous keying).
It will be applied after restarting CAN communication.
Behaviour
y37 = 0: Standard
y37 = 1: Compatible with LM1
Device type (0x1000) responses
0001 0192 (hex)
0000 0000 (hex)
Available PDOs
PDO1, PDO2, and PDO3
*PDO3 is configurable.
Only PDO1
*PDO1 is configurable.
Function code settings for PDO
ex. S01 = 0201 (hex)
ex. S01 = 0202 (hex)
y41
Setting method of speed command by communication
Specifies to use either speed command or acceleration command via RS-485 or CANopen
communication.
y41 data
Function
0
Speed command (S01, S21)
1
Acceleration command (S16, S17)
y95
Communication data storage selection
If any of the communication error alarms (
Er8
,
ErP
,
Ert
) occurs in RS-485 or CANopen
communication, the data of communication command function codes (S codes) can automatically be
cleared.
Since the frequency and operation commands are also disabled when the data is cleared, the inverter
does not start unintentionally when an alarm is released.
y95 data
Function
0
When a communication error alarm occurs, the function code Sxx data is not cleared
(compatible with the conventional mode).
1
When a communication error alarm occurs, the function codes S01, S05 and S21 data
is cleared.
2
When a communication error alarm occurs, the bits assigned in function code S06 for
operation command are cleared.
3
Clear operations of 1 and 2 above are performed.
2-138
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...