2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
When the reference speed (pre-ramp) is changed before the reference speed (final) reaches that
speed (pre-ramp) (during acceleration/deceleration)
The inverter immediately aims at the newly changed reference speed (pre-ramp), applying the
acceleration/deceleration times and S-curve acceleration/deceleration zones defined on the previous
page, just as when the reference speed (pre-ramp) is changed after the reference speed (final) reaches
the previously commanded reference speed (pre-ramp).
The differences between operations before and after the reference speed (final) reaches the speed
(pre-ramp) are as described below.
When the reference speed (pre-ramp) change yields deceleration during acceleration (Reference
speed (final) at the time of change > Reference speed (pre-ramp)), the inverter performs a short floor
operation.
Refer to the description of function code L29 for a short floor operation.
On the contrary, when the speed changes to acceleration during deceleration, the inverter
immediately starts S-curve acceleration, which may make an impact on the load.
Acceleration/deceleration times in S-curve operation
In an S-curve operation, the acceleration/deceleration time "t" can be calculated by the following
formulae.
- If the speed deviation exceeds the S-curve zone:
100
max
|
|
S2
S1
N
N1
N2
+
×
≥
−
T
S2
S1
N
N1
N2
t
×
+
+
−
=
100
max
- If the speed deviation is within the S-curve zone:
100
max
|
|
S2
S1
N
N2
N1
+
×
<
−
T
S2
S1
S2
S1
N
N1
N2
t
×
+
×
+
×
−
=
100
100
max
|
|
2
Where,
Nmax : Maximum speed (r/min)
N1
: Speed before the start of acceleration/deceleration (r/min)
N2
: Speed after the end of acceleration/deceleration (r/min)
S1
: S-curve zone (% of the maximum speed) at the start of acceleration (at the end of
deceleration)
S2
: S-curve zone (% of the maximum speed) at the end of acceleration (at the start of
deceleration)
T
: Acceleration period (s) required from 0.00 r/min to the rated speed (F03)
or
Deceleration period (s) required from the rated speed (F03) to 0.00 r/min
t
: Acceleration/deceleration period (s) required from N1 to N2
2-29
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...