2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
Function selection (F31)
F31 specify which data is monitored at the output terminals [FMA].
F31
data
[FMA] output
Data
Definition of monitor amount 100%
0
Reference speed
(Final) Output frequency of the inverter
(Equivalent to the motor rated speed)
Rated Speed (F03)
1
Primary frequency
Output frequency of the inverter
Rated Speed (F03)
2
Output current
Output current (RMS) of the inverter
Twice the inverter rated current
3
Output voltage
Output voltage (RMS) of the inverter
200 V class: 250 V
400 V class: 500 V
4
Output torque
Motor shaft torque
Twice the rated motor torque
8
Actual speed
Speed detected through the PG interface Maximum speed as 100%
9
DC link bus voltage
DC link bus voltage of the inverter
200 V class: 500 V
400 V class: 1000 V
10
Universal AO
Command from communication
(
RS-485 communication user
manual)
20,000/100%
14
Calibration (+)
For meter calibration
Full scale output
Always full scale (equivalent to
100%)
Output
18
Inverter heat sink
temperature
Heat sink detection temperature of
inverter
200°C/100%
19
Inverter internal
temperature
Internal detection temperature of
inverter
200°C/100%
111
Customizable logic
output signal 1
Only when analog output has been
defined.
100% / 100%
112
Customizable logic
output signal 2
Only when analog output has been
defined.
100% / 100%
113
Customizable logic
output signal 3
Only when analog output has been
defined.
100% / 100%
114
Customizable logic
output signal 4
Only when analog output has been
defined.
100% / 100%
115
Customizable logic
output signal 5
Only when analog output has been
defined.
100% / 100%
116
Customizable logic
output signal 6
Only when analog output has been
defined.
100% / 100%
117
Customizable logic
output signal 7
Only when analog output has been
defined.
100% / 100%
118
Customizable logic
output signal 8
Only when analog output has been
defined.
100% / 100%
119
Customizable logic
output signal 9
Only when analog output has been
defined.
100% / 100%
120 Customizable logic
output signal 10
Only when analog output has been
defined.
100% / 100%
F42
Control Mode
F42 selects the control mode.
Data for F42
Function
0
Vector control with PG for asynchronous motor
1
Vector control with PG for synchronous motor
2
Torque Vector control without PG for asynchronous motor
Refer to page 2-2 for the control mode of the inverter.
2-47
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...