Enable external alarm trip --
THR
(Function code data = 9)
Turning this terminal command OFF immediately shuts down the inverter output (so that the motor
coasts to a stop), displays the alarm OH2, and outputs the alarm relay (for any alarm)
ALM
. The
THR
is self-held, and is reset when an alarm reset takes place.
Use a trip command from external equipment when you have to immediately shut down
the inverter output in the event of an abnormal situation in a peripheral equipment.
■
Enable jogging operation --
JOG
(Function code data = 10)
Turning this terminal command ON enables jogging operation.
For details, refer to the description of function code C20 (Jogging Speed).
■
Enable communications link via RS485 or CAN --
LE
(Function code data = 24)
Turning this terminal command ON runs the motor according to the frequency commands or run
commands received via the communications link selected with function code H30 (RS485, CAN or
DCP).
No
LE
assignment is functionally equivalent to the
LE
being ON.
For details, refer to the description of function code H30 (Communications Link Operation).
■
Universal DI --
U-DI
(Function code data = 25)
Using
U-DI
enables the inverter to monitor digital signals sent from the peripheral equipment via an
RS485 or CAN communications link by feeding those signals to the digital input terminals. Signals
assigned to the universal DI are simply monitored and do not operate the inverter.
For an access to universal DI via the RS485 or CAN communications link, refer to their
respective Instruction Manuals.
■
Enable PG vector control --
PG/Hz
(Function code data = 27)
Turning this terminal command OFF cancels the PG vector control and switches to the V/f control.
The ON/OFF switching when the inverter is in operation will not be validated; it will become
effective after the inverter stops. Whenever this terminal command is not assigned, the PG vector
control is effective by default.
■
Torque Bias 1 and 2 --
TB1
and
TB2
(Function code data = 60 and 61)
Selecting
TB1
or
TB2
allows you to set digital torque bias.
For details, refer to the description of function code L54 (Torque Bias, Mode).
■
Hold torque bias --
H-TB
(Function code data = 62)
Turning this terminal command ON holds torque bias setting. Turning it OFF release the hold status.
For details, refer to the description of function code L55 (Torque Bias, Startup time).
■
Enable battery operation --
BATRY
(Function code data = 63)
Turning this terminal command ON selects operation by batteries.
For details, refer to the description of function code C03 (Battery Operation Speed).
2-52
Содержание Frenic lift
Страница 1: ...LM2A series Reference Manual INR SI47 1909a E...
Страница 7: ......
Страница 13: ......
Страница 51: ...2 38...
Страница 221: ......
Страница 242: ...3 4 Programming Mode Chap 3 OPERATION USING TP A1 LM2 Figure 3 14 Screen transition for Op Monitor display example 3 21...
Страница 252: ......
Страница 254: ...URL http www fujielectric com...