Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
256
Hauser
"Input values" submenu
"Current input 1 to n" submenu
Navigation: Expert → Sensor → Measured val. → Input values → Current input 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Measured val. 1 to n (1603–1 to n)
1: 6151 to 6152
2: 6153 to 6154
3: 6155 to 6156
Float
Read
Signed floating-point number
Measur. curr. 1 to n (1604–1 to n)
1: 6131 to 6132
2: 6133 to 6134
3: 6135 to 6136
Float
Read
0 to 22.5 mA
"Val.stat.inp. 1 to n" submenu
Navigation: Expert → Sensor → Measured val. → Input values → Val.stat.inp. 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Val.stat.inp. (1353–1 to n)
1: 2746
2: 4699
3: 4700
Integer
Read
0 = Low
1 = High
"Output values" submenu
"Value curr.out 1 to n" submenu
Navigation: Expert → Sensor → Measured val. → Output values → Value curr.out 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Output curr. 1 to n (0361–1 to n)
1: 5931 to 5932
2: 5933 to 5934
3: 5935 to 5936
Float
Read
0 to 22.5 mA
Measur. curr. 1 to n (0366–1 to n)
1: 5779 to 5780
2: 5781 to 5782
3: 5783 to 5784
Float
Read
0 to 30 mA
"PFS output 1 to n" submenu
Navigation: Expert → Sensor → Measured val. → Output values → PFS output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Output freq. 1 to n (0471–1 to n)
1: 3462 to 3463
2: 3464 to 3465
3: 9910 to 9911
Float
Read
0.0 to 12
500.0 Hz
Value per pulse (0455–1 to n)
Float
Read / Write
Switch status 1 to n (0461–1 to n)
1: 2485
2: 2486
3: 9917
Integer
Read
1 = Open
6 = Closed