Description
Use this function to enter the limit value for the switch-on value (process variable >
switch-on value = closed, conductive).
When using a hysteresis: Switch-on value > Switch-off value.
Dependency
The unit depends on the process variable selected in the
Assign limit
parameter
Switch-off value
Navigation
Expert → Output → PFS output 1 to n → Switch-off value (0464–1 to n)
Prerequisite
• In the
Operating mode
Switch
option is selected.
• In the
Switch out funct
Limit
option is selected.
Description
Use this function to enter the measured value for the switch-off point.
User entry
Signed floating-point number
Factory setting
Country-specific:
• 0 kg/h
• 0 lb/min
Additional information
Description
Use this function to enter the limit value for the switch-off value (process variable <
switch-off value = open, non-conductive).
When using a hysteresis: Switch-on value > Switch-off value.
Dependency
The unit depends on the process variable selected in the
Assign limit
parameter
Assign dir.check
Navigation
Expert → Output → PFS output 1 to n → Assign dir.check (0484–1 to n)
Prerequisite
• The
Switch
option is selected in the
Operating mode
parameter (→ 126).
• The
Fl. direct.check
option is selected in the
Switch out funct
Description
Use this function to select a process variable for monitoring the flow direction.
Selection
• Off
• Volume flow
• Mass flow
• Correct.vol.flow