Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
71
User entry
Max. 10 characters such as letters, numbers or special characters (@, %, /)
Factory setting
User mass
Additional information
Result
The defined unit is shown as an option in the choose list of the following parameters:
•
Mass flow unit
•
Mass unit
Example
If the text CENT for "centner" is entered, the following options are displayed in the picklist
for the
Mass flow unit
• CENT/s
• CENT/min
• CENT/h
• CENT/d
Mass offset
Navigation
Expert → Sensor → System units → User-spec. units → Mass offset (0562)
Description
Use this function to enter the zero point shift for the user-specific mass and mass flow
unit.
User entry
Signed floating-point number
Factory setting
0
Additional information
Description
Value in user-specific unit = (factor × value in base unit) + offset
Mass factor
Navigation
Expert → Sensor → System units → User-spec. units → Mass factor (0561)
Description
Use this function to enter a quantity factor (without time) for the user-specific mass and
mass flow unit.
User entry
Signed floating-point number
Factory setting
1.0
Additional information
Example
Mass of 1 Zentner = 50 kg → 0.02 Zentner = 1 kg → entry: 0.02