Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
272
Hauser
Navigation: Expert → Output → Relay output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Assign limit (0807–1 to n)
1: 8248
2: 8249
3: 8250
Integer
Read / Write
1 = Mass flow
2 = Volume flow
3 = Correct.vol.flow
4 = Density
5 = Ref.density
7 = Temperature
16 = Totalizer 1
17 = Totalizer 2
18 = Totalizer 3
66 = Pressure
73 = Concentration
74 = Target mass flow
75 = Carrier mass fl.
78 = Carrier vol. fl.
79 = Carr.corr.vol.fl
83 = Oil density
84 = Water density
86 = GSV flow
87 = GSVa
88 = Oil mass flow
89 = Water mass flow
90 = NSV flow
91 = NSVa
92 = S&W volume flow
93 = Ref.dens.altern.
94 = Oil corr.vol.fl.
95 = Water corr.v.fl.
96 = Targ.corr.vol.fl
97 = Target vol. flow
99 = Oil volume flow
100 = Oscil. damping
101 = Water cut
102 = Water vol. flow
Assign diag. beh (0806–1 to n)
1: 8245
2: 8246
3: 8247
Integer
Read / Write
0 = Alarm
1 = Warning
2 = Alarm or warning
Assign status (0805–1 to n)
1: 8272
2: 8273
3: 8274
Integer
Read / Write
0 = Low flow cut off
1 = Partial pipe det
Switch-off value (0809–1 to n)
1: 8260 to 8261
2: 8262 to 8263
3: 8264 to 8265
Float
Read / Write
Signed floating-point number
Switch-off delay (0813–1 to n)
1: 8254 to 8255
2: 8256 to 8257
3: 8258 to 8259
Float
Read / Write
0.0 to 100.0 s
Switch-on value (0810–1 to n)
1: 8233 to 8234
2: 8235 to 8236
3: 8237 to 8238
Float
Read / Write
Signed floating-point number
Switch-on delay (0814–1 to n)
1: 8266 to 8267
2: 8268 to 8269
3: 8270 to 8271
Float
Read / Write
0.0 to 100.0 s
Failure mode (0811–1 to n)
1: 8242
2: 8243
3: 8244
Integer
Read / Write
0 = Actual status
1 = Open
6 = Closed