Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
79
Additional information
Description
Flow override is active
• The diagnostic message diagnostic message
C453 Flow override
is displayed.
• Output values
– Temperature: proceeding output
– Totalizers 1-3: Stop being totalized
Positive zero return can also be enabled via the Status input:
Assign stat.inp.
"Low flow cut off" submenu
Navigation
Expert → Sensor → Process param. → Low flow cut off
‣
Low flow cut off
Assign variable (1837)
On value (1805)
Off value (1804)
Pres. shock sup. (1806)
Assign variable
Navigation
Expert → Sensor → Process param. → Low flow cut off → Assign variable (1837)
Description
Use this function to select the process variable for low flow cutoff detection.
Selection
• Off
• Mass flow
• Volume flow
• Correct.vol.flow
Factory setting
Mass flow
On value
Navigation
Expert → Sensor → Process param. → Low flow cut off → On value (1805)
Prerequisite
One of the following options is selected in the
Assign variable
• Mass flow
• Volume flow
• Correct.vol.flow