Description of device parameters
Proline Cubemass 300 Modbus RS485
152
Hauser
Assign status
Navigation
Expert → Output → Relay output 1 to n → Assign status (0805–1 to n)
Prerequisite
In the
Relay outp.func.
parameter (→ 149), the
Digital Output
option is selected.
Description
Use this function to select the device status for the relay output.
Selection
• Partial pipe det
• Low flow cut off
Factory setting
Partial pipe det
Switch-off value
Navigation
Expert → Output → Relay output 1 to n → Switch-off value (0809–1 to n)
Prerequisite
In the
Relay outp.func.
parameter (→ 149), the
Limit
option is selected.
Description
Use this function to enter the measured value for the switch-off point.
User entry
Signed floating-point number
Factory setting
Country-specific:
• 0 kg/h
• 0 lb/min
Additional information
Description
Use this function to enter the limit value for the switch-off value (process variable <
switch-off value = open, non-conductive).
When using a hysteresis: Switch-on value > Switch-off value.
Dependency
The unit is dependent on the process variable selected in the
Assign limit
parameter
Switch-off delay
Navigation
Expert → Output → Relay output 1 to n → Switch-off delay (0813–1 to n)
Prerequisite
In the
Relay outp.func.
parameter (→ 149), the
Limit
option is selected.
Description
Use this function to enter a delay time for switching off the switch output.
User entry
0.0 to 100.0 s
Factory setting
0.0 s