Description of device parameters
Proline Cubemass 300 Modbus RS485
164
Hauser
Telegram delay
Navigation
Expert → Communication → Modbus config. → Telegram delay (7146)
Description
Use this function to enter a delay time after which the measuring device replies to the
request telegram of the Modbus master. This allows communication to be adapted to slow
Modbus RS485 masters.
User entry
0 to 100 ms
Factory setting
6 ms
Failure mode
Navigation
Expert → Communication → Modbus config. → Failure mode (7116)
Description
Use this function to select the measured value output in the event of a diagnostic message
via Modbus communication.
Selection
• NaN value
• Last valid value
Factory setting
NaN value
Additional information
Options
• NaN value
The device outputs the NaN value
.
• Last valid value
The device outputs the last valid measured value before the fault occurred.
This effect of this parameter depends on the option selected in the
Assign diag. beh
parameter.
Bus termination
Navigation
Expert → Communication → Modbus config. → Bus termination (7155)
Description
Displays whether the terminating resistor is enabled or disabled.
User interface
• Off
• On
Factory setting
Off
8)
Not a Number