Description of device parameters
Proline Cubemass 300 Modbus RS485
182
Hauser
Failure mode
Navigation
Expert → Application → Totalizer 1 to n → Failure mode (0901–1 to n)
Prerequisite
One of the following options is selected in the
Assign variable
the
Totalizer 1 to n
submenu:
• Volume flow
• Mass flow
• Correct.vol.flow
• Target mass flow
• Carrier mass fl.
Description
Use this function to select how a totalizer behaves in the event of a device alarm.
Selection
• Stop
• Actual value
• Last valid value
Factory setting
Stop
Additional information
Description
This setting does not affect the failsafe mode of other totalizers and the outputs. This
is specified in separate parameters.
Selection
• Stop
The totalizer is stopped in the event of a device alarm.
• Actual value
The totalizer continues to count based on the actual measured value; the device alarm is
ignored.
• Last valid value
The totalizer continues to count based on the last valid measured value before the device
alarm occurred.
3.7.2
"Concentration" submenu
For detailed information on the parameter descriptions for the
Concentration
application package,refer to the Special Documentation for the device → 7
Navigation
Expert → Application → Concentration
‣
Concentration
3.7.3
"Petroleum" submenu
For detailed information on the parameter descriptions for the
Petroleum
application
package,refer to the Special Documentation for the device → 7
*
Visibility depends on order options or device settings