Proline Cubemass 300 Modbus RS485
Modbus RS485 Register Information
Hauser
271
Navigation: Expert → Output → PFS output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Assign status (0485–1 to n)
1: 3374
2: 3375
3: 4734
Integer
Read / Write
0 = Low flow cut off
1 = Partial pipe det
Switch-on delay (0467–1 to n)
1: 6247 to 6248
2: 6249 to 6250
3: 6251 to 6252
Float
Read / Write
0.0 to 100.0 s
Switch-off delay (0465–1 to n)
1: 6239 to 6240
2: 6241 to 6242
3: 6243 to 6244
Float
Read / Write
0.0 to 100.0 s
Failure mode (0486–1 to n)
1: 3384
2: 3385
3: 9912
Integer
Read / Write
0 = Actual status
1 = Open
6 = Closed
Switch status 1 to n (0461–1 to n)
1: 2485
2: 2486
3: 9917
Integer
Read
1 = Open
6 = Closed
Invert outp.sig. (0470–1 to n)
1: 2583
2: 2584
3: 9916
Integer
Read / Write
0 = Yes
1 = No
*
Visibility depends on order options or device settings
"Relay output 1 to n" submenu
Navigation: Expert → Output → Relay output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Terminal no. (0812–1 to n)
1: 8278
2: 8279
3: 8280
Integer
Read
0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
Relay outp.func. (0804–1 to n)
1: 2488
2: 2489
3: 9876
Integer
Read / Write
1 = Open
2 = Diag. behavior
3 = Fl. direct.check
4 = Limit
5 = Digital Output
6 = Closed
Assign dir.check (0808–1 to n)
1: 8251
2: 8252
3: 8253
Integer
Read / Write
0 = Off
1 = Mass flow
2 = Volume flow
3 = Correct.vol.flow