Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
181
Factory setting
Totalize
Additional information
Selection
Options
Description
Totalize
The totalizer is started or continues running.
Reset + hold
The totaling process is stopped and the totalizer is reset to 0.
hold
The totaling process is stopped and the totalizer is set to its defined start value
from the
Preset value
parameter.
Reset + totalize
The totalizer is reset to 0 and the totaling process is restarted.
totalize
The totalizer is set to the defined start value from the
Preset value
parameter and
the totaling process is restarted.
Hold
Totalizing is stopped.
Preset value 1 to n
Navigation
Expert → Application → Totalizer 1 to n → Preset value 1 to n (0913–1 to n)
Prerequisite
One of the following options is selected in the
Assign variable
the
Totalizer 1 to n
submenu:
• Volume flow
• Mass flow
• Correct.vol.flow
• Target mass flow
• Carrier mass fl.
Description
Use this function to enter a start value for the Totalizer 1 to n.
User entry
Signed floating-point number
Factory setting
Country-specific:
• 0 kg
• 0 lb
Additional information
Entry
The unit of the selected process variable is specified for the totalizer in the
Unit
totalizer
parameter (→ 178).
Example
This configuration is suitable for applications such as iterative filling processes with a fixed
batch quantity.
*
Visibility depends on order options or device settings