Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
225
Additional information
Description
The desired simulation value is defined in the
Switch status 1 to n
parameter.
Selection
• Off
Switch simulation is switched off. The device is in normal measuring mode or another
process variable is being simulated.
• On
Switch simulation is active.
Switch status 1 to n
Navigation
Expert → Diagnostics → Simulation → Switch status 1 to n (0463–1 to n)
Description
Use this function to select a switch value for the simulation. In this way, users can verify
the correct adjustment of the switch output and the correct function of downstream
switching units.
Selection
• Open
• Closed
Additional information
Selection
• Open
Switch simulation is switched off. The device is in normal measuring mode or another
process variable is being simulated.
• Closed
Switch simulation is active.
Relay out. 1 to n sim
Navigation
Expert → Diagnostics → Simulation → Relay out. 1 to n sim (0802–1 to n)
Description
Use this function to switch simulation of the relay output on and off. The display
alternates between the measured value and a diagnostic message of the "Function check"
category (C) while simulation is in progress.
Selection
• Off
• On
Factory setting
Off