Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
284
Hauser
Navigation: Expert → Diagnostics → Simulation
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Value curr.out 1 to n (0355–1 to n) 1: 5995 to 5996
2: 5997 to 5998
3: 5999 to 6000
Float
Read / Write
3.59 to 22.5 mA
FreqOutputSim 1 to n (0472–1 to n) 1: 6203
2: 6204
3: 6205
Integer
Read / Write
0 = Off
1 = On
Freq value 1 to n (0473–1 to n)
1: 6207 to 6208
2: 6209 to 6210
3: 6211 to 6212
Float
Read / Write
0.0 to 12
500.0 Hz
Puls.outp.sim. 1 to n (0458–1 to n)
1: 6215
2: 6216
3: 6217
Integer
Read / Write
0 = Off
1 = Down-count. val.
2 = Fixed value
Pulse value 1 to n (0459–1 to n)
1: 6219
2: 6220
3: 6221
Integer
Read / Write
0 to 65
535
Switch sim. 1 to n (0462–1 to n)
1: 6223
2: 6224
3: 6225
Integer
Read / Write
0 = Off
1 = On
Switch status 1 to n (0463–1 to n)
1: 6227
2: 6228
3: 6229
Integer
Read / Write
1 = Open
6 = Closed
Relay out. 1 to n sim (0802–1 to n)
1: 7523
2: 7524
3: 7525
Integer
Read / Write
0 = Off
1 = On
Switch status 1 to n (0803–1 to n)
1: 8239
2: 8240
3: 8241
Integer
Read / Write
1 = Open
6 = Closed
Puls.outp.sim. (0988)
5957
Integer
Read / Write
0 = Off
1 = Down-count. val.
2 = Fixed value
Pulse value (0989)
5973
Integer
Read / Write
0 to 65
535
Dev. alarm sim. (0654)
6812
Integer
Read / Write
0 = Off
1 = On
Event category (0738)
4261
Integer
Read / Write
0 = Sensor
1 = Electronics
2 = Configuration
3 = Process
Diag. event sim. (0737)
4259
Integer
Read / Write
• Off
• Diagnostic event picklist (depends on
the category selected)
*
Visibility depends on order options or device settings