Proline Cubemass 300 Modbus RS485
Modbus RS485 Register Information
Hauser
267
Navigation: Expert → Output → Curr.output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
20 mA value (0372–1 to n)
1: 5915 to 5916
2: 5917 to 5918
3: 5919 to 5920
Float
Read / Write
Signed floating-point number
Measuring mode (0351–1 to n)
1: 5899
2: 5900
3: 5901
Integer
Read / Write
0 = Forward flow
2 = Rev. flow comp.
13 = Forward/Reverse
Damping out. 1 to n (0363–1 to n)
1: 5903 to 5904
2: 5905 to 5906
3: 5907 to 5908
Float
Read / Write
0.0 to 999.9 s
Response time (0378–1 to n)
1: 5867 to 5868
2: 5869 to 5870
3: 5871 to 5872
Float
Read
Positive floating-point number
Failure mode (0364–1 to n)
1: 5911
2: 5912
3: 5913
Integer
Read / Write
0 = Min.
1 = Max.
4 = Actual value
5 = Last valid value
6 = Defined value
Failure current (0352–1 to n)
1: 5979 to 5980
2: 5981 to 5982
3: 5983 to 5984
Float
Read / Write
0 to 22.5 mA
Output curr. 1 to n (0361–1 to n)
1: 5931 to 5932
2: 5933 to 5934
3: 5935 to 5936
Float
Read
3.59 to 22.5 mA
Measur. curr. 1 to n (0366–1 to n)
1: 5779 to 5780
2: 5781 to 5782
3: 5783 to 5784
Float
Read
0 to 30 mA
*
Visibility depends on order options or device settings
"PFS output 1 to n" submenu
Navigation: Expert → Output → PFS output 1 to n
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Terminal no. (0492–1 to n)
1: 6551
2: 6552
3: 6553
Integer
Read
0 = Not used
2 = 24-25 (I/O 2)
3 = 22-23 (I/O 3)
Signal mode (0490–1 to n)
1: 6235
2: 6236
3: 6237
Integer
Read / Write
0 = Passive
2 = Active
Operating mode (0469–1 to n)
1: 4479
2: 4480
3: 9907
Integer
Read / Write
0 = Pulse
1 = Switch
12 = Frequency