Description of device parameters
Proline Cubemass 300 Modbus RS485
76
Hauser
Additional information
Result
The defined unit is shown as an option in the choose list of the
Pressure unit
Pressure offset
Navigation
Expert → Sensor → System units → User-spec. units → Pressure offset (0580)
Description
Use this function to enter the offset for adapting the user-specific pressure unit.
User entry
Signed floating-point number
Factory setting
0
Pressure factor
Navigation
Expert → Sensor → System units → User-spec. units → Pressure factor (0579)
Description
Use this function to enter a quantity factor for the user-specific pressure unit.
User entry
Signed floating-point number
Factory setting
1.0
Additional information
Example
1 Dyn/cm² = 0.1 Pa → 10 Dyn/cm² = 1 Pa → user entry: 10
3.2.3
"Process param." submenu
Navigation
Expert → Sensor → Process param.
‣
Process param.
Flow damping (1802)
Density damping (1803)
Temp. damping (1822)
Flow override (1839)