Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
111
• Water mass flow
• Oil volume flow
• Water vol. flow
• Oil corr.vol.fl.
• Water corr.v.fl.
• Concentration
• Temperature
• Carr. pipe temp.
• Electronic temp.
• Osc. freq. 0
• Osc. ampl. 0
• Freq. fluct. 0
• Osc. damping 0
• Osc.damp.fluct 0
• Signal asymmetry
• Exc. current 0
• Pressure
Factory setting
Mass flow
Current span
Navigation
Expert → Output → Curr.output 1 to n → Current span (0353–1 to n)
Description
Use this function to select the current range for the process value output and the upper
and lower level for signal on alarm.
Selection
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
• Fixed current
Factory setting
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
Additional information
Description
• In the event of a device alarm, the current output adopts the value specified in the
Failure mode
• If the measured value is outside the measuring range, the diagnostic message
S441 Curr.output 1 to n
is displayed.
• The measuring range is specified via the
0/4 mA value
20 mA value
"Fixed current" option
The current value is set via the
Fixed current
parameter (→ 112).
Example
Shows the relationship between the current span for the output of the process variable and
the lower and upper alarm levels:
*
Visibility depends on order options or device settings