Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
119
t
a =
b =
Q
0
+
-
2
1
A0028098
Q
Flow
t
Time
1
Lower range value (value assigned to 0/4 mA current)
2
Upper range value (value assigned to 20 mA current)
With
Forward flow
option
• a (—): The flow components outside the scaled measuring range cannot be taken into
account for signal output.
The diagnostic message
S441 Curr.output 1 to n
is displayed.
• b (- -): The current output signal is proportional to the process variable assigned.
t
I [mA]
a =
b =
A0028100
I
Current
t
Time
With
Forward/Reverse
option
This option is not possible in this case as the values for the
0/4 mA value
parameter
(→ 112) and
20 mA value
parameter (→ 114) have different signs.
With
Rev. flow comp.
option
Flow components outside the span are buffered, balanced and output after a maximum
delay of 60 s.
t
I [mA]
S = A
S
A
A0028101
I
Current
t
Time
S
Flow components saved
A
Balancing of saved flow components