Proline Cubemass 300 Modbus RS485
Description of device parameters
Hauser
77
‣
Low flow cut off
‣
Partial pipe det
Flow damping
Navigation
Expert → Sensor → Process param. → Flow damping (1802)
Description
Use this function to enter a time constant for flow damping (PT1 element). Reduction of
the variability of the flow measured value (in relation to interference). For this purpose,
the depth of the flow filter is adjusted: when the filter setting increases, the reaction time
of the device also increases.
User entry
0 to 100.0 s
Factory setting
0 s
Additional information
Description
The damping is performed by a PT1 element
.
User entry
• Value = 0: no damping
• Value > 0: damping is increased
Damping is switched off if
0
is entered (factory setting).
Result
The damping affects the following variables of the device:
Density damping
Navigation
Expert → Sensor → Process param. → Density damping (1803)
Description
Use this function to enter a time constant for the damping (PT1 element) of the density
measured value.
User entry
0 to 999.9 s
Factory setting
0 s
2)
Proportional behavior with first-order lag