Modbus RS485 Register Information
Proline Cubemass 300 Modbus RS485
252
Hauser
Navigation: Expert → System → Display
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Decimal places 4 (0119)
4051
Integer
Read / Write
0 = x
1 = x.x
2 = x.xx
3 = x.xxx
4 = x.xxxx
Display interval (0096)
3604 to 3605
Float
Read / Write
1 to 10 s
Display damping (0094)
3554 to 3555
Float
Read / Write
0.0 to 999.9 s
Header (0097)
3624
Integer
Read / Write
0 = Device tag
1 = Free text
Header text (0112)
3968 to 3973
String
Read / Write
Max. 12 characters such as letters,
numbers or special characters (e.g. @,
%, /)
Separator (0101)
3671
Integer
Read / Write
• . (point)
• , (comma)
Contrast display (0105)
3674 to 3675
Float
Read / Write
20 to 80 %
Backlight (0111)
3967
Integer
Read / Write
0 = Disable
1 = Enable
*
Visibility depends on order options or device settings
"Config. backup" submenu
Navigation: Expert → System → Config. backup
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Operating time (0652)
2631
Integer
Read
Days (d), hours (h), minutes (m) and
seconds (s)
Last backup (2757)
6430
Integer
Read
Days (d), hours (h), minutes (m) and
seconds (s)
Config. managem. (2758)
5500
Integer
Read / Write
0 = Cancel
1 = Execute backup
2 = Restore
4 = Clear backup
5 = Compare
Backup state (2759)
5502
Integer
Read
1 = Backup in progr.
2 = Restore in progr
4 = Delete in progr.
5 = Comp. in progr.
6 = Restoring failed
7 = Backup failed
251 = None
Compar. result (2760)
5514
Integer
Read
0 = Set. identical
1 = Set. not ident.
2 = No backup
3 = Check not done
4 = Backup corrupt
5 = Dataset incomp.
"Diagn. handling" submenu
Navigation: Expert → System → Diagn. handling
Parameter
Register
Data type
Access
Selection / User entry / User interface
→
Alarm delay (0651)
6808 to 6809
Float
Read / Write
0 to 60 s